BA254R/24/ae/09.07
71064276
SW version
2.01.00
Operating Instructions
RIA452
Process display
Page view 0
1 2 3 4 5 6 ... 79 80

Summary of Contents

Page 1 - Process display

BA254R/24/ae/09.0771064276SW version2.01.00Operating InstructionsRIA452Process display

Page 2 - Block circuit diagram

Wiring104 Wiring4.1 Quick wiring guideG09-RIA452ZZ-04-01-xx-en-000Fig. 4: Terminal assignment of the process display unit (universal input see Page 1

Page 3 - Table of contents

Wiring11Terminal assignmentTerminal Terminal assignment TypeL/L+ L for ACL+ for DCPower supplyN/L- N for ACL- for DCNC Not connectedJ1 Jumper for lock

Page 4 - 1 Safety instructions

Wiring1254 Normally closed (NC)Relay 455 Common (COM)56 Normally open (NO)141 Normally closed (NC)Relay 5 (optional)142 Common (COM)143 Normally open

Page 5 - Safety instructions

Wiring13Universal input option The device can be optionally equipped with a universal input instead of a current input.G09-RIA452xx-04-10-xx-en-002Fig

Page 6 - 2 Identification

Wiring14Terminal assignment4.2 Connecting the device "Caution!Do not install or wire the device when it is connected to the power supply. Failu

Page 7 - Identification

Wiring154.2.2 Connecting external sensors!Note! Active and passive sensors with analog, TC, resistance and RTD sensors can be attached to the device.D

Page 8 - 3 Installation

Wiring164.3 Post-connection checkDevice condition and specifications NotesIs the device or cable damaged (visual inspection)? -Electrical connection

Page 9 - Installation

Operation175Operation5.1 Quick operation guide M1 Analog inputINPUTSignal type Connection type*Curve Signal dampingSignal type Connection Curve DampDi

Page 10 - 4 Wiring

Operation18Value in the event of a faultSimulation mASimulation VoltFail value Simu mA Simu VM5 Digital input 1-4DIGITAL INP.Function digital input 1-

Page 11 - Terminal assignment

Operation19Reset totalizer Flow calculationDimension of input signalDimension of linearized valueDecimal point for formulaReset total Calc flow Dim. I

Page 12

Brief overviewFor rapid and easy commissioning:Block circuit diagramG09-RIA452xx-05-00-xx-en-000Fig. 1: RIA452 block circuit diagramSafety instructio

Page 13 - Universal input option

Operation20M20 Min/Max memoryMIN/MAXSignal source for Min/MaxDecimal pointDisplay minimum valueRef. min/max Dec. point Min. valueDisplay maximum value

Page 14 - 4.2 Connecting the device

Operation215.2 Display and operating elementsG09-RIA452xx-19-00-06-xx-000Fig. 9: Display and operating elements 1) Green operating indicator, lights

Page 15 - G09-RIA452xx-04-10-xx-en-003

Operation22Relay displayNo power to relay: no displayPower to relay: (symbol lit)Digital input status displayDigital input configured: (green)Sign

Page 16

Operation23B) Selection from list5.3.2 Entering textG09-RIA452ZZ-19-00-00-en-001Fig. 12: Entering text with RIA452G09-RIA452ZZ-19-00-00-xx-003Fig. 11:

Page 17 - 5Operation

Operation24Possible charactersThe following characters can be entered:Space +ABCDEFGHIJKLMNOPQRSTUVWXYZabcdefghijklmnopqrstuvwxyz0123456789/\%°23+-.;:

Page 18

Commissioning256 Commissioning6.1 Function check Make sure that all post-connection checks have been carried out before you commission your device:•

Page 19

Commissioning26Function (menuitem)Parameter setting DescriptionSignal type4 - 20 mA0 - 20 mA0 - 5 mA (*)0 - 100 mV (*)0 - 200 mV (*)0 - 1 V (*)0 - 10

Page 20

Commissioning27CurveLinearQuad.°C°FKelvin Linear or quadratic (quad.) characteristic of the sensor used. Can be selected for analog signals. °C, °F, K

Page 21 - 5.2.1 Display

Commissioning28Adjusting the analog inputThe input can be adjusted to the sensor with the aid of the following parameters.For current, voltage and res

Page 22 - 5.3 Local operation

Commissioning29Display sw.0 to 99 sec0Selectable period for displaying the individual values if combinations of display values have been selected unde

Page 23 - 5.3.2 Entering text

Table of contents1 Safety instructions . . . . . . . . . . 41.1 Designated use . . . . . . . . . . . . . . . . . . . . . . 41.2 Installation, co

Page 24 - Operation

Commissioning306.3.3 Analog output - ANALOG OUT/M3All configurable parameters for the analog output can be found under the analog output menu item whi

Page 25 - 6 Commissioning

Commissioning31Fail modeHoldconstMinMaxOutput value if a sensor or device error occurs.• Hold = last valid value• Const = freely selectable value• Min

Page 26 - Parameter setting Description

Commissioning326.3.4 Digital input - DIGITAL INP./M5The settings for the digital status inputs, e.g. for monitoring pumps, starting/stopping the count

Page 27

Commissioning33Pump monitoring functionIf pump monitoring should be implemented, digital inputs 1 to 4 are permanently assigned to relays 1 to 4. This

Page 28

Commissioning34In event 5, the alarm relay and the error message on the display are acknowledged by pressing the jog shuttle.In event 6 and 7, the unp

Page 29

Commissioning35!Note! A faulty pump is always brought back into service depending on the signal at the related digital input. Acknowledging the error

Page 30

Commissioning36FunctionOffMinMaxGradIn bandOut bandAlarmAlarm inverseSelects limit value and fault monitoring. In the event of device errors or incorr

Page 31

Commissioning37Sw. delay0..990The starting time for 24-hour counting can be selected with Sw. delay. Every time the instrument is reset, the process o

Page 32

Commissioning38Min operating modeG09-RIA452ZZ-15-00-xx-en-001Fig. 15: Min operating mode The following parameters must be configured:Menu Function (me

Page 33 - Commissioning

Commissioning39Max operating modeG09-RIA452ZZ-15-00-xx-en-002Fig. 16: Max operating mode The following parameters must be configured:Menu Function (me

Page 34

Safety instructions41 Safety instructionsSafe operation of the process display unit is only guaranteed if these Operating Instructions have been read

Page 35

Commissioning40Grad operating modeG09-RIA452ZZ-15-00-xx-en-006Fig. 17: Grad operating mode The "Grad" operating mode is used for monitoring

Page 36

Commissioning41• EEPROM HW error (E101)The relay remains picked up even after acknowledging.• Implausible calibration data (E103)The relay remains pic

Page 37

Commissioning42AlternateG09-RIA452ZZ-15-00-xx-en-007Fig. 19: Alternating pump controlAlternate switching is used to ensure that several pumps are util

Page 38 - Min operating mode

Commissioning43!Note! Relays not included in alternating pump control are available.This function cannot be applied to individual relays. Relays not i

Page 39 - Max operating mode

Commissioning446.3.6 INTEGRATION/M18This function can only be selected if the pulse output option is available in the device.!Note! If the preset coun

Page 40 - G09-RIA452ZZ-15-00-xx-en-006

Commissioning45Set count A9999990.0End value/start value for preset counter; refers permanently to relay 1.Set count B9999990.0Value for preliminary a

Page 41

Commissioning46Dim. flowm3/s, l/s, hl/s, igal/s, usgal/s, barrels/s, inch3/s, ft3/s, Usmgal/s, Ml/s, m3/smin, l/min, hl/min, igal/min, usgal/min, barr

Page 42 - Alternate

Commissioning47Flumes weirKha VenturiISO VenturiBST VenturiParshallPalmer-BowRect. WTORect WThrNFXRectWTONFXRectWThrTrap.W TOV-weirBST V-weirNFX V-wei

Page 43 - G09-RIA452ZZ-15-00-xx-en-009

Commissioning48BST Venturi4"7"12"18"30"Venturi channels as per British Standard4" = Venturi channel as per British Stand

Page 44

Commissioning49Rect.WThr2H3H4H5H6H8HTOT52TRectangular weir with constriction2H = rectangular weir with constriction 2H3H = rectangular weir with const

Page 45

Safety instructions51.5 Notes on safety conventions and iconsThe safety instructions in these Operating Instructions are labeled with the following sa

Page 46

Commissioning50Integration functionWith this function, the computed value from the linearization table or the current flow value for channel calculati

Page 47 - ISO Venturi

Commissioning51Thus, the number of free relays available is reduced accordingly. The operating menus for these inputs/outputs are then hidden.Set coun

Page 48 - Rect.WTO

Commissioning526.3.8 Min/Max memory - MIN MAX/M20The process display unit can save a minimum and a maximum measured value. The input signal or the sig

Page 49

Commissioning536.3.9 Linearization table - LIN. TABLE/M21To linearize input variables, a linearization table can be saved in the measuring instrument,

Page 50 - NFX V-weir

Commissioning54Tank linearizationExample:G09-RIA452ZZ-15-00-xx-xx-011Fig. 22: Example for tank linearizationYou want to determine the amount of cereal

Page 51

Commissioning55– Level 10 m– Numeric display should show 1500 (m3)– Bar graph should show 100% – 20 mA should be present at the analog outputThe follo

Page 52

Commissioning566.3.10 Support points of linearization table - LINPOINTS 1..X/M23..MXXDisplays the set value pairs of the linearization table. This men

Page 53

Commissioning57VersionV X.XX.XX Version of the device software currently installed.Func. alt.TimeCountSetting for controlling pump rotation in alterna

Page 54

Maintenance587 MaintenanceNo special maintenance work is required on the device.8 AccessoriesName Order No.ReadWin® 2000 PC configuration software and

Page 55

Troubleshooting599 TroubleshootingThe following section provides you with an overview of possible causes of errors to provide you with an initial trou

Page 56

Identification62 Identification2.1 Device designation2.1.1 NameplateCompare the nameplate on the device with the following diagram:G09-RIA452xx-18-00-

Page 57

Troubleshooting60!Note! The errors specified above can be evaluated with a relay in the operating mode "Alarm" and "Alarm inverse"

Page 58 - 8 Accessories

Troubleshooting619.3 Spare partsG09-RIA452ZZ-09-00-xx-xx-000Fig. 23: RIA452 spare partsItem No. Name Order No.1 Housing front RIA452X-HA2 Housing seal

Page 59 - 9 Troubleshooting

Troubleshooting629.4 ReturnFor a return, e.g. in case of repair, the device must be sent in protective packaging. The original packaging offers the be

Page 60 - 9.2.2 Incorrect entries

Technical data6310 Technical data10.1 Input10.1.1 Measured variableCurrent (standard)Digital inputs (standard)Current/voltage, resistance, resistance

Page 61 - 9.3 Spare parts

Technical data6410.1.4 Performance characteristicsReference operating conditionsPower supply: 230 V AC ±10%, 50 Hz ±0.5 HzWarm-up period: 90 minAmbien

Page 62 - 9.5 Disposal

Technical data65Current output:Accuracy Thermocouples Type J (Fe-CuNi), -210 to 999.9 °C (-346 to 1382 °F) (IEC584)± (0.15% oMR +0.5 K (0.9 °F)) from

Page 63 - 10 Technical data

Technical data66Voltage output10.1.5 Power supplyElectrical connectionG09-RIA452ZZ-04-01-xx-en-000Fig. 24: Terminal assignment of process display unit

Page 64

Technical data67Universal input optionThe device can be optionally equipped with a universal input instead of a current input.G09-RIA452xx-04-10-xx-en

Page 65 - Current output:

Technical data6810.2 Output10.2.1 Output signalRelay, transmitter power supply (standard)Current, voltage, pulse, intrinsically safe transmitter power

Page 66 - Electrical connection

Technical data69Hysteresis:• 0 to 99%Signal source:s• Analog input signal• Integrated value• Digital inputNumber:• 4 in basic unit (can be extended to

Page 67 - Technical data

Identification72.3 Certificates and approvalsCE mark, declaration of conformityThe process display unit is designed to meet state-of-the-art safety re

Page 68 - 10.2 Output

Technical data7010.3.2 EnvironmentAmbient temperature range-20 to +60 °C (-4 to 140 °F))Storage temperature-30 to +70 °C (-22 to 158 °F)Operating heig

Page 69 - 10.3 Installation

Technical data7110.4 Mechanical construction10.4.1 Design, dimensionsG09-RIA452ZZ-06-01-xx-xx-000Fig. 26: Dimensions of the process display unitG09-RI

Page 70

Technical data7210.4.2 WeightApprox. 500 g (17.64 oz)10.4.3 Material• Housing front: ABS plastic, galvanized• Housing casing: plastic PC10GF10.4.4 Ter

Page 71 - 10.4 Mechanical construction

Technical data73– Measuring range overshoot/undershoot10.5.2 Operating elementsJog/shuttle dial10.5.3 Remote operationConfigurationThe device can be c

Page 72 - 10.5 Human interface

Technical data7410.7 Documentation System components - display unit, top-hat rail devices, overvoltage protection and energy computer (FA016K) Suppl

Page 73

Appendix7511 Appendix11.1 Flow conversionConversion of various units to m3/hLiter• 1 l/s = 3.6 m3/h• 1 l/min = 0.06 m3/h• 1 l/s = 0.001 m3/hHectoliter

Page 74 - 10.7 Documentation

76IndexNumerics0% value (function). . . . . . . . . . . . . . . . . . . . . . . 27100% value (function). . . . . . . . . . . . . . . . . . . . . 272

Page 75 - 11 Appendix

GGamma (function) . . . . . . . . . . . . . . . . . . . . . . . 46Grad. Time (function). . . . . . . . . . . . . . . . . . . . . 57HHardware lockin

Page 76

78Prog. name (function) . . . . . . . . . . . . . . . . . . . . . 56Pulse outputParameter. . . . . . . . . . . . . . . . . . . . . . . . . . . . 51P

Page 78

Installation83 Installation3.1 Installation conditionsThe permitted ambient conditions (see Section 10 "Technical data") must be observed wh

Page 79

CanadaUSAEndress+Hauser Canada1075 Sutton DriveBurlington, ON L7L 5Z8 CanadaTel. 905-681-9292800-668-3199Fax 905-681-9444www.ca.endress.comEndress+Hau

Page 80 - FM+SGML6.0 ProMoDo

Installation91. Push the device with the sealing ring (item a) through the panel cutout from the front.2. Keep the device horizontal and suspend the t