Wiring
14
Terminal assignment
4.2 Connecting the device
"
Caution!
Do not install or wire the device when it is connected to the power supply. Failure to comply
with this precaution can result in irreparable damage to the electronics.
4.2.1 Connecting the power supply
"
Caution!
Before wiring the device, ensure that the supply voltage corresponds to the specification on
the nameplate.
For the 90 to 250 V AC version (power supply connection), a switch marked as a separator,
as well as an overvoltage organ (rated current 10 A), must be fitted in the supply line near
the device (easy to reach).
G09-RIA452xx-04-10-xx-xx-000
Fig. 6: Connecting the power supply
Terminal Terminal assignment
11 + 0/4 to 20 mA signal
12 Signal ground (current, voltage, temperature)
13 + 1 V, + thermocouples, - resistance thermometer signal (3/4 wire)
15 + resistance thermometer signal (4-wire)
17 + 30 V
19 + resistance thermometer power supply (3-wire/4-wire)